The CMM-2.2 mobile oil plant removes solid particles, water and gases from dielectric insulation oil.
The plant is used for installation, repairs and operation of oil filled high voltage equipment (power transformers, high voltage switches etc).
Operating conditions:
- ambient temperature from 278 to 313°К (+5 to + 35°C/ 8°F to 104°F;
- atmospheric pressure 84 to 106.7 kPa (630 to 800 mm. );
- elevation up to 2000 meters/6561 feet above sea level;
- outdoors and under canopy;
- indoors with adequate
TECHNICAL SPECIFICATIONS OF CMM-2.2
Parameter
|
Value |
Capacity, m3/hour / gals. per hour: |
|
- thermal vacuum drying mode;
|
2.2/582.34
|
|
1.0/264.7
|
Processed oil parameters*: |
|
- mass moisture content, g/ton, max
|
10
|
- filtration fineness, micron
|
5
|
|
1.5
|
Max oil output temperature in heating mode, ºС/ ºF |
60/140
|
Min outlet pressure, MPa |
0.2
|
Oil heater power, kW max |
36
|
Max power consumption, kW |
40
|
Electric power |
|
|
380
|
|
50/60
|
Dimensions, mm/ft |
|
|
1550/5’1’’
|
|
1000/3’3’’
|
|
1850/6’1’’
|
Note: * Parameters indicated in the table are possible with the
following initial conditions:
• volumetric gas content – below 10.5%
• mass moisture content – below 0.005% (50 g/ton)
• temperature – above 0 ºС/32 ºF
• with initial heating of oil in the unit to +60± 5оС/ 140°± 9оF.
**All equipment sold in the USA is designed to operate on 60 Hz
AC Power