CMM-4/7 OIL PROCESSING UNIT

    GlobeCore

    LEAVE A MESSAGE


    Please fill this line so we can call out to you by name

    Please fill this line so we can answer your questions

    Please fill this line so we can call you back


    This CMM 4/7 mobile oil processing unit is designed for degassing, removal of solids and heating of oil for power transformers with voltage up to 1,150 kV.

    The unit can be used to:
    1) heat electrical systems that contain insulating oil with hot oil;
    2) for vacuum drying of transformers and
    3) for vacuumizing.

    The unit is best suited to facilities that install, repair and service oil filled electric power transformers and other oil filled electrical equipment.

    The unit is not certified for use in and around explosive gases, toxic gases or other aggressive environments.

    When indoors or other enclosed spaces, exhaust gases must be vented to the outside through hoses or pipelines.

    TECHNICAL SPECIFICATIONS OF CMM-4/7 Oil Degassing Unit

    Parameters Value
    Capacity, m3/hour / gals. per hour:
    • degassing, nitrogenation, drying and filtration mode
    4/1059.0
    • heating and filtration mode
    7/1853.0
    Capacity adjustment range, m3/hour / gals. per hour: 0-4.0/0.0-1059.0
    Processed oil parameters*:
    • volumetric gas content %, max
    0.1
    • mass moisture content, g/ton, max
    10
    • ISO 4406 purity class
    9
    • solid particle content, g/ton, max
    8
    • filtration fineness, micron
    1
    • dielectric strength, kV, min
    70
    Oil temperature in heating mode, ºС/ ºF 90/194
    Filtration rate ≥50
    Outlet pressure, MPa 0.35
    Oil output head, meters/yards 35.0/38.3
    Oil heater power, kW 50
    Oil heater mean surface power, W/cm2, max 1.15
    Max power consumption, kW 60
    Electric power
    • voltage, V
    400
    • AC frequency, Hz**
    50/60
    Dimensions, mm/ft
    • length
    3250/10’8’’
    • height
    1940/6’4’’
    • width
    1800/5’11’’
    Weight, kg/lbs 1270/2,806.7

    Note: * initial oil parameters:

    • volumetric gas content – below 5%;
    • mass moisture content – below 01% (100 g/ton);
    • temperature – above 0 ºС/ 32 ºF.

    **All equipment sold in the USA is designed to operate on 60 Hz AC Power