Parameter
|
Value
|
| Rate of vapor-gas mix evacuation from transformer tank at residual pressure from atmospheric to 400 Pa, liters/second, min |
27×3=81
|
| Rate of vapor gas mix evacuation from transformer tank at residual pressure from 400 Pa to 26 Pa, liters/second, min |
500
|
| Residual pressure created by vacuum pump in transformer tank, max |
26 |
| Residual pressure in the unit during air leak test, Pa, max |
4 |
| Air leak in one hour, Pa, max |
100 |
| Water vapor condensation surface temperature, °С/ °F, max |
-70/-94 |
| Residual moisture content in solid insulation, %, max |
1.0 |
| Cold generation capacity (at -70°С/-94F), W |
600 |
| Condensation surface area, m2, min |
6.1 |
| Defrosting system power consumption, kW |
2.1 |
| Nominal power, kW |
21 |
| Power supply voltage at 50Hz/ 60Hz, V (fully customizable on request) |
380 |
| Dimensions, mm/ft, max |
| • length
• width
• height |
1700/5’57’’
1600/5’25’’
1950/6’4’’
|
| Weight, kg/lbs, max |
2100/4,641 |